技术参数
型号 可调整设定范围 死区 工作压力***
上升时为设定点范围高压端
下降时为设定点范围低压端
H100K 型 psid bar psi bar psi bar
540 0.2 to 7 “wcd 0,5 to 17,4 mbar 0.05 to 0.6 “wc 0,1 to 1,5 mbar 30 “Hg Vac to 200 -1 to 13,8
541 1 to 20 “wcd 2,5 to 49,8 mbar 0.1 to 1.0 “wc 0,2 to 2,5 mbar 30 “Hg Vac to 200 -1 to 13,8
542 5 to 50 “wcd 12,4 to 124,5 mbar 0.2 to 2.5 “wc 0,5 to 6,2 mbar 30 “Hg Vac to 200 -1 to 13,8
543 10 to 200 “wcd 24,9 to 497,8 mbar 0.5 to 8 “wc 1,2 to 19,9 mbar 30 “Hg Vac to 200 -1 to 13,8
544 2 to 20 0,1 to 1,4 0.1 to 1.3 6,9 to 89,6 mbar 30 “Hg Vac to 1200 -1 to 82,7
545 5 to 50 0,3 to 3,4 0.2 to 2.2 13,8 mbar to 0,1 30 “Hg Vac to 1200 -1 to 82,7
546 10 to 125 0,7 to 8,6 0.4 to 5.0 27,6 mbar to 0,3 30 “Hg Vac to 1200 -1 to 82,7
547 50 to 250 3,4 to 17,2 0.8 to 10 0,1 to 0,7 30 “Hg Vac to 1200 -1 to 82,7
548 100 to 500 6,9 to 34,5 2. 0 to 15 0,1 to 1,0 30 “Hg Vac to 1200 -1 to 82,7
差压开关工作原理
差压开关由2个膜盒腔组成,两个腔体分别由两片密封膜片和一片感差压膜片密封。高压和低压分别进入差压开关的高压腔和低压腔,感受到的差压使感压膜片形变,通过栏杆弹簧等机械结构,终启动上端的微动开关,使电信号输出。
防爆差压开关的特点
1. 动作点稳定,不会受冲击、振动温度变化或其它环境条件影响。
2. 不会因压力的波动而引起接点抖动,清晰明朗的开或关状态。
3. 不受泵的冲击、接点的振动疲劳等的影响。
4. 寿命长,稳定性及动作重复性高。